Emergency and exit lighting testing

Routine testing of emergency lights and exit signs in Melbourne buildings: what the test involves, the standard, who may repair fittings and published costs.

Emergency and exit lighting testing switches each emergency light and exit sign to battery power, checks it stays lit for the required time, and logs any fitting that fails. Emergency lighting and exit signs are both essential safety measures under Schedule 8 of the Building Regulations 2018, and their routine service is set out in AS/NZS 2293.2.

Illustrative photo for Emergency and exit lighting testing

Why these fittings fail

Emergency lights and exit signs sit idle on charge for months. The faults show up only when mains power is cut:

  • batteries that have aged and no longer hold charge
  • lamps or LED drivers that have failed
  • fittings disconnected during a fit-out or ceiling repair
  • signs painted over, blocked by shelving or hung signage
  • fittings removed when a tenancy was refitted, leaving a path with no light

A building usually finds out about a failed fitting at the test, which is why the testing records matter for the annual report.

What the standard covers

AS/NZS 2293.2 is the Australian and New Zealand Standard for routine service and maintenance of emergency lighting and exit signs. Standards Australia describes it as setting the periodic inspection and maintenance procedures that keep emergency evacuation lighting ready for operation at all times. You can see the summary on the Standards Australia store listing for AS/NZS 2293.2. Your maintenance schedule tells you which edition and frequency apply to your building. The Melbourne cost guide we rely on describes the test as six-monthly with an annual test.

Test methods compared

Method How it works Good for Watch for
Manual test Technician cuts power to each circuit or uses test switches, times the discharge and walks every fitting Small sites with few fittings Labour time, and every fitting must be reachable
Self-test fittings Each fitting runs its own test and shows a status light Medium sites, retrofits Someone still has to read and record each fitting
Monitored system A central panel or software logs each fitting’s test result Large sites and towers Software records must still reach the log book

All three can produce compliant records. What matters for the annual report is a dated record for every fitting, the result, and what was done about each failure.

What a provider checks

  1. A fitting list or plan that matches what is installed, with locations numbered.
  2. Each fitting runs on battery for the full test and is still lit at the end.
  3. Exit signs are visible from the path of travel and not obstructed.
  4. Charge indicators show normal after the test.
  5. Fittings that failed are tagged and listed with location and fault.
  6. Records are signed and filed for the annual essential safety measures report.

Who can repair or replace fittings?

Testing and reading results is inspection work. Replacing a fitting, changing wiring, or adding new emergency lights is electrical work, and in Victoria that falls under the Electricity Safety Act 1998 and Energy Safe Victoria. Energy Safe says electricians must work for a Registered Electrical Contractor to do work for a customer, and the contractor or licensed worker completes a Certificate of Electrical Safety for the electrical work and gives a copy to the customer. Its guide to certificates of electrical safety explains what the customer should receive. You can check a contractor on the Energy Safe public registers.

Keep the fitting list current

A test is only as good as the list behind it. Each time a tenancy is refitted, a ceiling is replaced or a wall is moved, fittings can be added, relocated or lost. Ask the provider to number every fitting on a floor plan, compare it with what they find on the day, and flag any location where the plan and the building disagree. A gap between the plan and the ceiling is something to raise with the building surveyor, because the approved layout is what the annual report is measured against. Updated plans also make next year’s test quicker.

What a careful provider will not do

  • Record a pass from a status light without running the test.
  • Leave failed fittings off the record because a repair quote is pending.
  • Replace a fitting without the electrical licence and certificate the work needs.
  • Remove an exit sign during a fit-out without the building surveyor’s say. Regulation 227 keeps measures in their approved locations.

Melbourne buildings and lighting loads

Apartment towers in Southbank can carry hundreds of fittings across stairs, car parks and corridors, while a shop on a Richmond or Chapel Street strip may have two exit signs and one emergency light. Car parks and open stairwells expose fittings to damp, so failures cluster there.

Cost

A published Melbourne cost guide prices exit and emergency light testing on a small site at $110 to $250 per visit, as a flat visit charge. Larger sites are charged per fitting, and repairs or replacement fittings are extra. Compare quotes on the same fitting count; the Melbourne cost guide page covers this.

Next step

Count the exit signs and emergency lights, note any known failures, and send a lighting test enquiry. You arrange the test and any repairs directly with the independent provider who responds; Melbourne Essential Safety only handles the enquiry. If your exits also need checking, read about path of travel inspections.

Send a job enquiry

Frequently asked questions

What does a discharge test do?

It cuts mains power to the fittings so they run on their batteries, then checks each one is still lit at the end of the required period. A fitting that dims or goes out early has failed and needs repair.

Will the test interrupt our business?

Ask the provider how circuits will be isolated and whether normal lighting is affected. Testing can be planned in sections or outside trading hours where the building needs it.

Do LED exit signs still need testing?

Yes. LED fittings still rely on batteries and electronics that age. Every emergency light and exit sign listed for the building is tested regardless of the lamp type.

Who should replace a failed exit sign?

A licensed electrician working for a Registered Electrical Contractor. Ask for the Certificate of Electrical Safety where the work requires one, and add the repair record to the log book.