Fire door and smoke door inspections

Annual fire door and smoke door inspections for Melbourne apartments and commercial buildings: what is checked, common defects, rules, standards and costs.

A fire door inspection confirms that each fire door, smoke door and required solid core door still closes by itself, latches, seals and keeps its fire rating. These doors and their closers and latches are essential safety measures under Schedule 8 of the Building Regulations 2018, so owners must maintain them and report yearly.

Illustrative photo for Fire door and smoke door inspections

Which doors are covered?

Part 1 of Schedule 8 lists the door items under building fire integrity:

  • fire doors, including sliding fire doors and their warning systems, with self-closing, automatic closing and latching mechanisms
  • solid core doors with their self-closing, automatic closing and latching mechanisms
  • smoke doors with their self-closing, automatic closing and latching mechanisms
  • fire windows and fire shutters, which are usually checked on the same visit

Part 3 adds the warning signs on sliding fire doors and signs telling people not to impair the operation of doors. In apartment buildings the entry doors to each unit are often fire-rated or solid core doors, so a 40-unit block may have more doors to check than any other measure.

Signs a fire door needs attention

  • It is wedged, chocked or hooked open.
  • It does not close fully from wide open, or closes and bounces back off the latch.
  • The closer arm is disconnected, leaking oil or missing.
  • There are holes from removed locks, peepholes, cat flaps, hooks or extra hardware.
  • Smoke seals or intumescent strips are torn, painted over or missing.
  • The gap at the bottom has grown after new flooring went down.
  • The compliance tag on the door edge or frame has been painted over or removed.
  • A tenant has replaced the door or lockset during a fit-out.

What a provider checks

Check What passes Common fail
Self-closing Door closes fully from any open position Weak or disconnected closer
Latching Latch engages every time without a push Misaligned strike plate, worn latch
Door leaf No holes, cuts or unapproved hardware Removed deadbolt left a hole, new peephole fitted
Frame and hinges Secure, no gaps opened up Loose frame after building movement
Seals Present and undamaged where fitted Torn or painted smoke seals
Hold-open devices Release on alarm where fitted Magnetic hold-opens not releasing
Tags and signs Door and frame identification intact, required signs in place Tags painted over

Fire-resistant doorsets are built and installed to AS 1905.1, the Australian Standard that sets requirements for their construction and installation. Routine inspection, testing and maintenance of fire protection systems and equipment is covered by AS 1851. The building’s maintenance schedule says which standard and frequency apply to your doors. Both are listed in the Standards Australia store, for example AS 1905.1 fire-resistant doorsets.

Repair or replace?

Most defects are fixed on the spot or on a return visit: adjusting or replacing a closer, realigning a strike, replacing seals. A damaged leaf, holes through the door, or a non-compliant replacement door usually means a new fire-rated doorset. Ask the provider to separate:

  1. adjustments done during the inspection
  2. repairs quoted as a follow-up
  3. items that need a replacement doorset and, where the work goes beyond like-for-like, advice from a building surveyor

What a careful provider will refuse

  • Drilling a fire door to fit a deadbolt, peephole or hook without confirming the door keeps its rating.
  • Removing a closer so a door stays open for convenience.
  • Passing a door with a missing or unreadable tag without recording that the evidence is missing.
  • Filling holes with ordinary filler and calling the door compliant.
  • Moving a fire door or smoke door from its approved location. Regulation 227 only allows measures to be moved for inspection, testing or maintenance.

Owners corporations and fire doors

In a subdivided apartment building the owners corporation usually carries the owner’s duties for common property, and the City of Monash’s essential safety measures page warns that penalties can be served on building owners and/or the owners corporation. Unit entry doors are a frequent dispute because residents change them. A careful inspection report names the unit, the defect and the photo, which gives the committee what it needs to follow up.

Melbourne buildings where this matters

Walk-up flats and apartment towers carry the most doors. Our pages on South Yarra and Box Hill cover the local building types. Older converted warehouses often have fire doors added at different times, so tags and hardware vary from door to door.

Cost

A published Melbourne cost guide puts annual fire door inspection at $25 to $75 per door. Repairs and replacement doorsets are extra and are quoted after the inspection. The Melbourne ESM cost guide shows how door counts add up across a year of servicing.

Next step

Count the fire and smoke doors if you can, note any you know are damaged, and request a fire door inspection quote. The site passes your request on; the independent inspector you deal with sets the price, does the inspection and stands behind the report. The results feed straight into the annual essential safety measures report.

Send a job enquiry

Frequently asked questions

How do I know if a door is a fire door?

Fire doors usually carry a compliance tag or label on the door and on the frame. The maintenance schedule and building plans will also identify required fire and smoke doors. If tags are painted over, an inspector can often still find them.

Can an apartment owner change their front door?

If the entry door is a required fire or solid core door, any replacement must meet the same requirements, and the owners corporation should be told first. Swapping in an ordinary door creates a defect the owners corporation will have to deal with.

Is a door wedge on a fire door ever acceptable?

No. A fire door that is wedged open cannot stop smoke or fire. If a door needs to stay open for daily use, a building surveyor can advise on hold-open devices that release automatically when the alarm activates.

Can a fire door with a hole be patched?

Small repairs may be possible with products approved for that door, but many holes mean the doorset has lost its rating and must be replaced. A careful inspector will tell you which situation you are in rather than covering it over.

How many fire doors does a typical apartment block have?

It varies with the design. Count the stair doors on each level, any corridor smoke doors, services cupboard doors and, where required, each unit's entry door. Ask the provider to quote on that count.