Exit and path of travel inspections
Routine egress inspections for Melbourne buildings: clear exits, working exit doors and paths to the street, who is responsible, and what an inspector checks.
An egress inspection checks that every required exit, the path of travel to it and the route from it to the street are open, working and clear. In Victoria the occupier carries this duty day to day under regulation 228 of the Building Regulations 2018, and the owner reports on exits as essential safety measures each year.

Who is responsible for exits?
Two people hold separate duties, and both can be fined.
- The occupier of a Class 1b, 2, 3, 5, 6, 7, 8 or 9 building, or a place of public entertainment, must keep all exits, paths of travel to exits, and paths from exits across the land to a road readily accessible, functional and clear of obstructions (regulation 228).
- The owner must keep the exits, exit doors and their hardware maintained so they fulfil their purpose (regulation 226), and include them in the annual essential safety measures report.
In a tenanted office or shop, the tenant is usually the occupier. In an apartment block, the owners corporation looks after common corridors and stairs, and each resident still must not block them. The City of Casey’s maintenance of essential safety measures page also lists giving access to private areas for ESM inspections and maintenance among an occupier’s responsibilities.
What counts as an exit or path of travel?
Part 2 of Schedule 8 to the regulations lists the means of egress items treated as essential safety measures:
- paths of travel to exits
- discharge from exits, including the path from open space to the public road
- exits themselves, including fire-isolated and non fire-isolated stairs and ramps, stair treads, balustrades and handrails, and fire-isolated passageways
- smoke lobbies to fire-isolated exits
- open access ramps or balconies for fire-isolated exits
- doors in or leading to a required exit that are not fire or smoke doors, with their closing and latching hardware
Exit signs and direction signs sit in Part 3 of the same schedule and are checked on the same walk.
What an inspector checks
| Area | Typical faults found | Why it matters |
|---|---|---|
| Corridors and aisles | Stock, bins, bikes, pallets or furniture narrowing the path | People must be able to move to an exit in smoke or darkness |
| Exit doors | Extra bolts or padlocks, hardware that needs a key from inside, doors that stick or drag | A door that cannot be opened quickly is not an exit |
| Fire stairs | Storage under or on landings, doors propped open, damaged treads or nosings | Fire-isolated stairs only work if the doors close and the stair stays clear |
| Handrails and balustrades | Loose fixings, missing sections | Falls in a crowded stair |
| Discharge to the street | Car parking, skips, gates or fencing locked across the route | The path must reach a road, not stop at a locked yard |
| Signs | Dark or obscured exit and direction signs | Covered under emergency and exit lighting testing |
The inspector records each fault, who needs to act and whether it was fixed on the day. Where a path is blocked by a tenant, the record is what lets the owner show they acted.
How often?
The frequency comes from the building’s maintenance schedule or maintenance determination, which sets the type and frequency of inspection for each measure. Many owners and managers book these walks more often than the annual report because blocked exits come back quickly in busy buildings. If you do not know your frequency, start with an ESM audit and maintenance schedule.
What the work involves
- The inspector walks every floor from the furthest point of each tenancy to the street, following the exit route.
- Each exit door is opened from the inside without a key and allowed to close.
- Stair doors, smoke lobby doors and their closers are checked for closing and latching. Fire doors get a more detailed check, set out in our fire door inspection guide.
- Treads, handrails and balustrades on exit stairs are looked over for damage.
- Faults are photographed and logged, and occupiers are told what to clear.
- The record goes into the building’s log book for the annual report.
What a careful provider will not do
- Record an exit as clear when it was blocked on the day and cleared only because the inspector asked.
- Fit or approve a lock, chain or bolt on an exit door to stop theft or after-hours entry. Security changes to an exit door belong with a building surveyor.
- Treat a fire stair as a storage room, even for a short time.
- Sign off a path that ends at a locked gate.
Melbourne buildings where this comes up
Busy retail strips, shop-top tenancies and older buildings with narrow rear lanes tend to collect obstructions at back doors and in loading areas. Apartment towers see bicycles and furniture in fire stairs and corridors after move-ins. See the local notes on our Richmond page and Southbank page.
Cost
We found no published Melbourne price for a standalone egress walk. Most providers include it in routine ESM servicing or the annual inspection. The cost guide lists the published ranges for yearly servicing by building type.
Next step
Ask for routine exit and egress inspections through the enquiry form, with the number of floors, tenancies and exits, and how often your schedule asks for checks. Inspections, records and pricing are handled by the independent provider who takes on the request.
Frequently asked questions
- Can I lock an exit door at night for security?
Not in a way that stops people inside getting out. Exit doors must stay usable as exits. If security is a concern, talk to a building surveyor about hardware that keeps the door secure from outside while still opening from inside.
- Is storing items under the fire stairs allowed?
No. Fire-isolated stairs and exit routes must be kept clear. Storage in or under an exit stair adds fuel and narrows the path, and the occupier can be fined for an obstructed exit.
- Who pays for clearing a blocked exit in a tenanted building?
Usually the occupier who caused it, as the occupier has the legal duty to keep exits clear. Leases often say more. The owner should still record the fault and follow it up, because the owner reports on exits each year.
- Do path of travel checks include the route outside the building?
Yes. The duty extends from the exits across the land to a road. Gates, parked vehicles, skips and fencing on that route are checked as well as the inside of the building.