Find help with essential safety measures inspections for Melbourne properties.

Essential safety measures inspections and annual reports

Annual essential safety measures inspections and AESMR preparation for Melbourne commercial, strata and public buildings, with the rules, timing and costs.

An essential safety measures inspection checks that each fire and life safety item listed for a building has been inspected, tested and maintained over the year, so the owner can sign the annual essential safety measures report (AESMR). In Victoria the report is required under regulation 223 of the Building Regulations 2018 for buildings that have essential safety measures.

Illustrative photo for Essential safety measures inspections and annual reports

Which buildings need an annual report?

According to the Building and Plumbing Commission (BPC), only houses and outbuildings sit outside the essential safety measures rules. The regulations name the classes: Class 1b, 2, 3, 5, 6, 7, 8 and 9 buildings, any Class 4 part of a building, and places of public entertainment (regulation 213). In practice that covers apartment blocks, offices, shops, cafes, warehouses, factories, car parks, hotels, aged care, schools, clinics and halls. The BPC lists the classes in plain terms on its building classifications page.

The measures themselves come from Schedule 8 of the regulations. It groups them into:

  • building fire integrity, such as fire doors, smoke doors, fire shutters and fire-rated penetrations
  • means of egress, such as exits, paths of travel and the doors in them
  • signs, including exit and direction signs
  • emergency lighting
  • fire fighting services, such as hydrants, hose reels, sprinklers and extinguishers
  • air handling and smoke control systems
  • detection and alarm systems, and occupant warning systems
  • lifts with fire service controls, standby power, and building clearance

Your building has only the items its occupancy permit, maintenance determination or maintenance schedule lists. A small shop may carry exit signs, an extinguisher and one rear door. A tower may carry most of the list.

When is the report due?

Timing is set by the building’s history, not by the calendar year.

Building When the AESMR must be prepared Where the list of measures comes from
Built or altered since 1 July 1994 with measures on the occupancy permit Within the 28 days before each anniversary of the first occupancy permit or maintenance determination that required a measure Maintenance schedule issued with the occupancy permit
Built before 1 July 1994 Within the 28 days before 13 June each year Measures required under the law at the time, often never written down
Both, where an older building was later altered Each list is reported on its own anniversary Both sources, which is why an audit helps

If no one knows the anniversary date, the occupancy permit or the council’s building file usually shows it. Our page on ESM audits and maintenance schedules covers buildings where the paperwork is missing.

What does the inspection cover?

A provider works through the maintenance schedule item by item. For each measure they confirm it is still in its approved location, that it works, and that the service records for the year are complete. Typical checks include:

  1. Exits and paths of travel are clear, and doors open in the direction and with the hardware approved.
  2. Fire and smoke doors close and latch on their own. Our fire door inspection guide explains the detail.
  3. Exit signs and emergency lights pass their tests. See emergency and exit lighting testing.
  4. Extinguishers, hose reels, hydrants and sprinklers have current service tags and records.
  5. Detection panels, warning systems and smoke control have been tested by the people licensed to work on them.

Many measures need more frequent attention than once a year. The maintenance schedule sets the frequency and type of inspection, testing and maintenance for each item. Where an occupancy permit calls up the 2005 or an earlier edition of AS 1851, regulation 196 lets the owner follow AS 1851-2012 instead, and Regulation 217 does the same for a maintenance determination. An owner who switches must keep following the 2012 edition for that measure.

What goes in the AESMR?

Regulation 224 lists what the report holds. It uses the BPC’s approved form, carries the owner’s signature and gives the building address. It must state that the owner has taken all reasonable steps to make sure each measure is operating, has been maintained so it can fulfil its purpose, and has been inspected, tested and maintained as the Act and regulations require. If the owner is following AS 1851 (2012 edition) instead of the schedule’s original frequencies, the report says so. The BPC publishes the annual essential safety measures report template.

The owner signs. An agent such as a specialist maintenance contractor can complete the report for the owner, as the BPC guide to essential safety measures explains, but the duty stays with the owner.

Who can do the inspection?

Victoria does not create a single licence for ESM inspections. The City of Monash notes that owners may inspect and test their own measures and complete the approved form, and it highly recommends a qualified ESM contractor for moderate to complex buildings. Some measures can only be serviced by licensed people:

  • Hydrants, hose reels and sprinklers are fire protection work under the Plumbing Regulations 2018, done by a plumber registered or licensed in that class.
  • Repairs to exit signs and emergency lights are electrical work under the Electricity Safety Act 1998.

A careful provider will tell you which items they will inspect themselves and which records they will collect from other licensed contractors.

What a careful provider will not do

  • Sign or draft a report for a measure nobody inspected, or for a period with missing records.
  • Tick a fire door or exit as compliant when it is wedged open or blocked on the day.
  • Leave a defect off the report because it is expensive to fix.
  • Remove or relocate a measure. Regulation 227 says measures stay in their approved location except while they are inspected, tested or maintained.

Records you must keep

Regulation 225 requires the owner to have these available at the building within 24 hours if the municipal building surveyor or the chief officer of the fire authority asks for them: every AESMR from the past 10 years, the maintenance schedules, any maintenance determinations, and the records of all inspection, testing, maintenance and repairs. A log book kept on site is the usual way to meet this. The offences in these regulations carry penalties of up to 20 penalty units, and councils and the fire authority can issue infringement notices.

What it costs

A published Melbourne cost guide puts the report for a small commercial building at $200 to $450 per report, plus GST, with larger buildings quoted individually. Servicing each measure is charged on top. The Melbourne ESM cost guide sets out the servicing ranges and how to compare quotes.

Next step

Gather the occupancy permit, the maintenance schedule and last year’s report, then send the details of the building through the enquiry form. Independent ESM providers who cover your area review the request and quote for themselves; this site does not carry out inspections. Owners in the city centre can also read the Melbourne area page.

Send a job enquiry

Frequently asked questions

How long before the anniversary should I book the inspection?

The report has to be prepared in the 28-day window before the anniversary date, so book the inspection early enough to fix defects before then. Allowing a couple of months gives time for repairs and for chasing records from other contractors.

Can I sign the annual report myself without a contractor?

Yes, the owner is the person who signs, and an owner can inspect a simple building personally. You must still be able to show records of inspection, testing and maintenance for every measure. Larger buildings with fire services usually need several licensed contractors.

Do I lodge the AESMR with council?

The regulations require the report to be prepared, signed and produced on request. Some councils also run their own lodgement page, so check with the council for your address. Either way, keep the signed copy and supporting records at the building.

What happens if a defect is found during the inspection?

It should be recorded with its location and fixed by the right trade. The report should reflect the real state of the measures. Fixing defects before the report is prepared is the clean way to handle it.

Does a single-tenancy shop need an annual report?

If the building has essential safety measures required by its occupancy permit, a maintenance determination or the older rules, yes. Even a small shop with exit signs, an emergency light and an extinguisher has measures to maintain and report on.